Hello Hans,

My comments are going to point in a slightly different direction than what you took here.

1. As strange as it sounds, I think that small (sub 10 MW) diesel generators should be considered in Figure 3.

2. MCC is more realistic than LEOC to be sure; but it looks at peak hours. And those peak hours are likely to have some sunshine.

3. 8760 coverage matters entirely. With those CHRs, something must cover all load for all hours.

4. Diesel generators have a short time horizon, low CapEx, moderate FOM and high fuel costs. The ELCC would be close to 1.00, no? I would think that the MCC would be very competitive.

5. The hybrid that I think will win will be diesel generators offset by BTM renewable generation (and probably BESS for smoothing).

6. There are references missing on Pages 17 and 18 of the PDF (in bold).

7. Efficiency. Always efficiency.

Very nice work! It is great to see how this is moving forward.